762mm for other spaces specified in sections 3011 e 2 and 3011 e 3.
Elevator machine room door requirements.
We usually have a large 4 0 single door.
After the last sentence add.
If access to the machine room is across a roof a stairway with a swing door shall be provided to the roof from the floor below roof access hatches are not permitted.
For facilities not located in a flood zone locate hydraulic elevator machine rooms on the lowest landing served by the elevator.
D the common wall floor or ceiling between the machine room and the hoistway is properly fire stopped.
An elevator machine room must be provided for each individual elevator or elevator group.
Access doors shall be provided for all elevator machine rooms or enclosures and shall conform to the following.
Although asme a17 1 allows doors to machine rooms to have a width of 29 5 inches the ibc requires a minimum clear width of 32 inches.
The elevator machine and controller must be located in the elevator machine room.
The american society of mechanical engineers publishes the construction standards for elevator equipment rooms.
Location of machinery spaces machine rooms control spaces control rooms and equipment 2 7 6 1.
Elevator safety is a critical consideration for builders who have state safety codes to follow permits to obtain and regular inspections to pass.
Fire extinguisher provided in the machine control room asme a17 1 rule 8 6 normally operable door closer with self locking lockset from within machine room provided asme a17 1 rule 2 7 3 4 machine control room provides 19 foot candles of illumination at floor level asme a17 1 rule 2 7 9.
Building the rooms to code means following the proper asme.
On our projects we rarely have elevator machine rooms with double doors.
C 1 2 elevator machine room requirements 1.
When doors need to be rated a 1 hour door is sufficient for a 2 hour rated room.
We always put an exit device on the inside of the door and swing the door out of the room so that if someone is injured while working on the elevator equipment they can get out without trying to grasp the hardware and pull the door open.
Only elevator related equipment is allowed inside the control room.
Iii in all other cases the machine room and access door must have the same rating as the machine room hoistway enclosure.
Location of machine rooms and control rooms.
Provide light switch and 110 vac gfi outlet in the control room with switch located adjacent to the door.
762mm and a minimum height of 6 ft 1 83m for machine rooms and a minimum height of 30 in.
Condition triggers 1 or 1 hour.